RWA-Kompaktzentrale 24VDC 4A VdS geprüft

WindowMaster RWA control panel WSC 304

24VDC 4A

2383
WSC 304 6101
This article is currently not available!

Leave your email address and stay informed about this article.

as soon as the item is back in stock
as soon as the item drops in price
as soon as the item is available as a special offer
scope of application - 1 SHE / ventilation group - Control of drives up to 4A - with... more

scope of application
- 1 SHE / ventilation group
- Control of drives up to 4A
- with microcontroller technology
- Smoke extraction of small and medium-sized construction objects
- expandable with additional plug-in modules
- Incl. 2 pieces of emergency power batteries

RWA compact control panel for controlling 24 VDC actuators for the smoke extraction function combined with daily ventilation.
By using modern microcontroller technology, the controller meets the requirements for the realization of smaller objects of construction, e.g. Staircase control smoke removal
facilities, sports halls, restaurants etc.
By cascading (linking) several controllers, even larger building objects can be realized in a decentralized system (master / slave module WSA 301 required).

Features
- Smoke control combined with ventilation
- built-in emergency power supply for min. 72 hours by battery backup
- Line monitoring SHE button
- Line monitoring RWA detector (if used)
- Monitoring the drive supply line
- Breakage of detector lines 1 and 2 separately visible
- Fault indication via diagnostic LEDs
- Fault message also programmable as SHE activation
- SHE activation at temperature within the control panel greater than 72 ° C
- Surface or flush mounting
- Version in flush-mounted housing with white surface-mounted frame
- Protection class IP30

connection options
- Drive with limit switch or electronic load shutdown
- Triggered by BMA via potential-free contact (BMZ module type WSA 306 required)
- With comfort ventilation, signals from BMS systems can be received
- Wind / rain detector can be connected without additional module
- 15 pieces ventilation button with display or any number of buttons without display
- 10 automatic detectors type WSA 300 61 or WSA 310
- 4 RWA main control panels type WSK 320 or type WSK 321
- 15 RWA secondary control panels type WSK 330

Technical advice

+49 9282 48731-15
technik@bsc-technology.de

Fast delivery

... of goods in stock. Orders placed before 14:00 are usually shipped the same day.

Questions about the article

to the inquiry form

SHEVS in stairwells usually have to provide 1m² of geometric smoke extraction area. The question often arises as to how this is actually calculated. We investigate this topic and bring light into the darkness.
Technical data more
Voltage : 230V AC
Protection class : IP 30
Number of SHEV buttons : any
Number of automatic detectors : 10
Ventilation button quantity : 15
Emergency operation : > 72 St
Ambient temperature : +10°C - +45°C
Scope of delivery: RWA-Kompaktzentrale mit 2 Notstromakkus 12V/2Ah (WSA 002)
Dimensions: 368x353x95mm
Output current: 4A
SHEV groups: 1
Ventilation groups: 1
Audits: ohne VdS-Zulassung