SIMON PROtec compact control panel SHEV
The SHEV® compact control panel is the heart of the SIMON PROtec SHEV system for stairwells. This is a compact unit designed in accordance with DIN EN 12101 Part 9 and Part 10.
The control unit contains a primary and secondary power supply as well as the entire control and regulation technology for operating 24 volt DC drives for building openings. The compact control unit controls the drives in the event of fire and for daily ventilation. Special ventilation functions (gap ventilation, dead man function, automatic ventilation) are freely and individually programmable for the user. The ventilation function is at the same time a daily function control of the SHEV system. Manual or automatic triggering of the smoke and heat ventilation activates servomotors or fittings that release the openings in the wall or roof area intended for smoke extraction.
Compact central system forsmoke and heat ventilation
The SHEV is specially designed for smoke and heat ventilation applications in stairwells and provides all the necessary connections for triggering devices (manual pushbuttons, smoke detectors, thermal detectors and fire alarm systems). Designed for daily ventilation applications, appropriate components can be connected: Wind/rain detectors, ventilation pushbuttons, EIB KNX modules, timers and higher-level controls. The connection lines for SHEV buttons, on-site contacts for triggering and motors are monitored. Remote diagnosis via GPRS allows optional maintenance and fault diagnosis without costly travel.
Easy control by status LEDs
Checking the functionality is easier than ever. The SHEV compact control panel is equipped with status LEDs on the motherboard (GREEN = I. O.; YELLOW = N.I.O.; RED = SHEV alarm triggered).
A connected ventilation pushbutton with OPEN/CLOSED function can be assigned or selected with different action behaviors. The selection options are configured with the selection switch SW1 on the SHEV® board. In the event of a power failure, the emergency power supply ensures the function of the SHEV system for at least 72 hours.
Advantages at a glance
- contains primary and secondary power supply as well as the entire control and regulation technology
- special ventilation functions freely and individually programmable
- daily function check of the SHEV system
- for use in stairwells
- contains all necessary connections for tripping devices
- Connection for external components
- Emergency power supply for at least 72 hours
- Control of functionality via status LEDs
Technical data
- Input voltage: 230 V AC
- Output voltage: 24 V DC
- Output current: 3 A / 6 A
- LED indicators: Ready for operation, Fault,Smoke triggered
- Ambient temperature range: -5 °C - 40 °C
- Mounting type: surface mounted/under plaster
- Housing: plastic, sheet steel RAL 9010
- Connections: Smoke vent button: 1 main and max. 7 secondary control points (type HE-075, HE-076), fan button (type DT, ST), thermal detector (type TH 70 Ö, TH 4860), smoke detector (type RM-3000, RM-2860), wind/rain detector (type WTS-892, WT-890), potential-free external activation
Technical advice
+49 9282 48731-15
technik@bsc-technology.de
Fast delivery
... of goods in stock. Orders placed before 14:00 are usually shipped the same day.
Questions about the article
Made in : | Germany |
Voltage : | 230V AC |
Number of SHEV buttons : | Smoke vent button: 1 main and max. 7 secondary control stations (type HE-075, HE- 076), fan button (type DT, ST) |
Number of automatic detectors : | Thermal detectors (type TH 70 Ö, TH 4860), smoke detectors (type RM-3000, RM-2860), wind/rain detectors (type WTS-892, WT-890), potential-free external activation |
Emergency operation : | min. 72 hours |
Output : | 24 V DC smoothed, stabilized |
Ambient temperature : | - 5° to + 40° C |
Color: | RAL7035 |
Scope of delivery: | Control panel, batteries, installation manual |
Dimensions: | WxHxD 254 x 180 x 111 mm |
Output current: | 3A |
SHEV groups: | 1 |
Ventilation groups: | 1 |
Audits: | DIN EN 12101 part 9 and 10 |
Scope of delivery
Control panel, batteries, installation manual