Wind and rain control WRS 2b In the event of wind / rain, a closing command is sent to SHEV... more
Wind and rain control WRS 2b
- In the event of wind / rain, a closing command is sent to SHEV control panels or ventilation control units. Four separate potential-free changeover contacts (output contacts) provide the required signal. The contacts remain active as long as a sensor has responded, but at least for 6 minutes
- Connection of a wind sensor WM or rain sensor RS is required
- Wind and rain sensitivity adjustable
- Selectable functions:
- - "Reduced wind sensitivity" (to close, equally strong wind must last longer)
- - "Continuous heating" (the rain sensor is heated continuously)
- - "Contact programming" (contacts 3 and 4 switch alternatively in case of wind and/or rain)
- - "Output deactivated" (deactivate all output contacts for service / maintenance purposes)
- - "Reduced closing time" (the minimum closing time is reduced from 6 to 3 minutes)
- - "Fault contact" (contact 2 switches in the event of a rain sensor fault)
- - "Test" (mode for testing the function of sensors and drives)
- Displays for operation I, wind W and rain R
- Plastic housing, light gray (RAL 7035)
Technical data:
- Mains voltage supply: 230 V~ / 50 - 60 Hz
- Power consumption: 0,09 A
- Dimensions in mm (W x H x D): 165 x 155 x 75
- Cable feed through membrane grommets (from below): 4 x M16
- Ambient temperature: -5 °C ... +40 °C
- Relative humidity: 20 % ... 80 %, non-condensing
- Housing protection class (according to DIN EN 60529): IP40 (Option SG: IP54)
- Not suitable for outdoor use. Protect from direct sunlight, moisture and excessive dust! Preferably, installation should take place in dry, heated rooms.
- The controller complies with the requirements of the directives 2006/95/EC and 2004/108/EC (interference emission: EN 61000-6-3 and EN 55022, interference immunity: EN 61000-6-2 and EN 50130-4).
- Inputs / outputs, fuses:
- Wind sensor WM, heated rain sensor RS: 1 each
- Adjustment range of wind sensitivity: approx. 5 - 15 m/s (approx. 20 - 60 km/h, about wind force 3 - 7)
- Adjustment range of rain sensitivity: light - heavy rain
- 4 change-over contacts, load capacity: 5 A / 30 V- / 230 V~
- Output contacts (G-fuse link 5 x 20 mm): F1 - F4: F 5 A
- Mains primary (G-fuse link 5 x 20 mm): F5: T 125 mA
Data sheet/instructions can be found under "Downloads".
Photos, videos and diagrams: Source © K+G Pneumatik GmbH
Technical advice
+49 9282 48731-15
technik@bsc-technology.de
Fast delivery
... of goods in stock. Orders placed before 14:00 are usually shipped the same day.
Questions about the article
What do you have to look out for when you want to connect a wind and/or rain detector to a SHEV control panel or ventilation system? We will give you a few tips to ensure that you choose the right product.
Technical data more
Scope of delivery: | Control |
Dimensions: | in mm (W x H x D): 165 x 155 x 75 |
Scope of delivery & accessories more